(2) Removing the corner cover and
indicator cover
a) While lightly pressing the cen-
ter of the corner cover, pull up
the tab for the screw hole.
Use the same procedure to
remove the indicator cover.
(Fig. 6-16)
3-6-2. Installing the Ceiling Panel
(1) Hang the temporary latches on the inside of the ceil-
ing panel to the receptacle on the unit to temporarily
attach the ceiling panel in place. (Fig. 6-17)
G
The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the ceiling panel corner with the
correct positions on the unit.
(2) Align the panel installation holes and the unit screw
holes. (Fig. 6-18)
(3) Tighten the supplied special screws at the 4 panel
installation locations so that the panel is attached
tightly to the unit.
G
Check that the wiring connectors are not caught
between the unit and the ceiling panel.
(4) Check that the panel is attached tightly to the ceiling.
(Fig. 6-19)
G
At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between
the ceiling panel and the ceiling surface.
G
If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling.
CAUTION
If the screws are not sufficiently tightened,
trouble such as that shown in the figure
below may occur. Be sure to tighten
the screws securely.
Air leakage
Air leakage from
ceiling surface
Staining
Condensation, water leakage
Corner cover
Indicator cover
If a gap remains between the ceiling
surface and the ceiling panel even
after the screws are tightened,
adjust the height of the unit again.
Adjust so that there are no gaps.
Fig. 6-20
9
1
Press
2
Pull up
Fig. 6-16
Temporary
latch
Fig. 6-17
Refrigerant tubing joint
REF.PIPE mark
Ceiling panel
Special screws
Fig. 6-18
Indoor unit
Ceiling surface
Fig. 6-19
The height of the unit can be adjusted from the ceiling
panel corner hole, with the ceiling panel attached, to
an extent that does not affect the unit levelness,
the drain hose, or other elements.
Temporary latches
Drainage check
DRAIN mark
Panel installation hole
(4 locations)
w
Do not allo
gaps
Ceiling panel