The value of "Moisture removal" for MSZ-GE24NA and MSY-GE24NA has been corrected. [2.7 pt./h 5.1 pt./h] Revision D: • MSZ-GE06/09/12/15/18NA- and MSY-GE09/12/15/18NA- have been added. TECHNICAL CHANGES MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-GE24NA 1. New model MSZ-GE06NA MSZ-GE06NA - MSZ-GE09NA MSZ-GE09NA -...
SPECIFICATION MSZ-GE09NA MSZ-GE12NA Indoor model MSZ-GE06NA MSY-GE09NA MSY-GE12NA Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay)/ Disconnect switch A Min. circuit ampacity Fan motor F.L.A 0.76 COOL Dry 399-321-237-170-145 Airfl ow (Wet) CFM (364-286-201-134-109) Super High - High - Med. -...
Page 6
14.5 21.0 The coverage should be used only as a general guideline since it varies accord- HEAT 20.6 29.5 ing to the size of the room and furniture MSZ-GE09NA 16.3 23.5 MSY-GE09NA arranged inside the room. COOL 14.5 21.0 HEAT 20.6...
SERVICE FUNCTIONS MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-GE24NA 7-1. TIMER SHORT MODE For service, the set time can be shortened by bridging of JPG and JPS the indoor electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) •...
Page 13
7-3. AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in the same mode just before the shut-off of the main power. Operation If the main power has been cut, the operation settings remain.
MICROPROCESSOR CONTROL MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-GE24NA WIRELESS REMOTE CONTROLLER E.g.: MSZ type MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA Signal transmitting section Operation display section OPERATE/STOP FAN SPEED CONTROL button (ON/OFF) button...
Page 15
INDOOR UNIT DISPLAY SECTION Operation Indicator lamp The operation indicator at the right side of the indoor unit indicates the operation state. • The following indication applies regardless of shape of the indication. Indication Operation state Room temperature Lighted Blinking Not lighted About 4°F(2°C) or more The unit is operating to...
Page 16
8-3. HEAT ( ) OPERATION (MSZ) (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone. (2) Select HEAT mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 61 ~ 88°F (16 ~ 31°C).
Page 17
8-6. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ) Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation. Mode selection (1) Initial mode When unit starts the operation with AUTO operation from OFF: • If the room temperature is higher than the set temperature, operation starts in COOL mode. •...
Page 18
(4) VANE AUTO ( ) mode The microprocessor automatically determines the vane angle to make the optimum room temperature distribution. In COOL and DRY operation In HEAT operation Vane angle is fixed to Horizontal position. Vane angle is fixed to Angle 5. Horizontal position (5) STOP (operation OFF) and ON TIMER standby...
Page 19
8-8. TIMER OPERATION 1. How to set the time (1) Check that the current time is set correctly. NOTE: Timer operation will not work without setting the current time. Initially “0:00 AM” blinks at the current time display of TIME MONITOR, so set the current time correctly with CLOCK SET button. How to set the current time (a) Press the CLOCK set button.
Page 20
8-9. SMART SET ( ) OPERATION (MSZ-GE06/09/12/15/18NA MSY-09/12/15/18NA) 1. How to SET SMART SET operation (1) Press OPERATE/STOP (ON/OFF) button. (2) Select COOL, HEAT (MSZ) or ECONO COOL mode. (3) Press SMART SET button. (4) Set the temperature, fan speed, and airfl ow direction for SMART SET operation. NOTE: •...
TROUBLESHOOTING MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-GE24NA 9-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn OFF the unit first with the remote controller, and then after confirm- ing the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
Page 22
9-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can be recalled. MSZ-GE06/09/12/15/18NA MSZ-GE24NA 1.
Page 23
2. Indoor unit failure mode table Upper lamp of OP- Abnormal point ERATION INDICA- Condition Remedy (Failure mode) TOR lamp Not lighted Normal — — The room temperature thermistor short or 1-time fl ash every Room temperature Refer to the characteristics of the room temperature open circuit is detected every 8 seconds dur- 0.5-second thermistor...
Page 24
9-3. INSTRUCTION OF TROUBLESHOOTING Start Indoor unit operates. Indoor unit does Indoor unit oper- OPERATION INDICATOR Outdoor unit does ates. not receive the lamp on the indoor unit is not operate normally. signal from re- Outdoor unit fl ashing ON and OFF. does not operate.
Page 25
9-4. TROUBLESHOOTING CHECK TABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes. OPERATION INDICATOR Lighted Blinking...
Page 26
fi rst has manual. setting not operate. the priority. 9-5. TROUBLE CRITERION OF MAIN PARTS MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-GE24NA Part name Check method and criterion Figure Measure the resistance with a tester.
9-6. TROUBLESHOOTING FLOW A Check of indoor fan motor MSZ-GE06/09/12/15/18NA MSY-GE09/12/15/18NA The indoor fan motor error has occurred, and the indoor fan does not operate. Turn OFF the power supply. Pay enough attention to the high voltage on the fan motor connector. Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch.
Page 28
MSZ-GE24NA MSY-GE24NA The indoor fan motor error has occurred, and the indoor fan does not operate. Turn OFF the power supply. Pay enough attention to the high voltage on the fan motor connector. Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch.
Page 29
B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner. MSZ-GE06/09/12/15/18NA MSY-GE09/12/15/18NA Press OPERATE/STOP (ON/OFF) 1 Look at the image of the signal transmitting section of button on the remote controller. the remote controller through the monitor of a digital camera or a camera phone.
Page 30
C Check of indoor P.C. board and indoor fan motor MSZ-GE06/09/12/15/18NA MSY-GE09/12/15/18NA Turn OFF the power supply. Remove indoor fan motor connector CN211 from indoor power P.C. board and vane Measure the resistance of indoor fan Short circuit: motor connector CN151 from the indoor motor.
Page 31
MSZ-GE24NA MSY-GE24NA Turn OFF the power supply. Remove indoor fan motor connector CN211 and Short circuit: Measure the resistance between CN211 Replace the indoor fan motor. vane motor connector CN151 from the indoor electronic of the indoor fan motor connector. control P.C.
Page 32
D How to check miswiring and serial signal error MSZ-GE06/09/12/15/18NA Turn OFF the power supply. MSY-GE09/12/15/18NA Is there rated voltage in the power supply? Check the power supply. Turn ON the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Check the wiring.
Page 33
MSZ-GE24NA MSY-GE24NA Turn OFF the power supply. Is there rated voltage in the power supply? Check the power supply. Turn ON the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Check the wiring. Press EMERGENCY OPERATION switch once. Does the OPERATION INDICATOR lamp light up? <Confi...
Page 34
E Electromagnetic noise enters into TV sets or radios Is the unit grounded? Ground the unit. Is the distance between the antennas Extend the distance between the antennas and and the indoor unit within 9.91 ft.(3 m), the indoor unit, and/or the antennas and the or is the distance between the antennas outdoor unit.
Page 35
9-7. Test point diagram and voltage MSZ-GE06/09/12/15/18NA/NA- MSY-GE09/12/15/18NA/NA- 1. Indoor power P.C. board, Indoor terminal P.C. board Indoor terminal P.C. board Indoor power P.C. board Varistor (NR11) Resistor (R111) Fuse (F11)( ) Indoor fan motor (CN211) 294/325 VDC (–) GND (high- voltage DC) 15 VDC (+)3-6 VDC...
Page 36
MSZ-GE06/09/12/15/18NA- MSY-GE09/12/15/18NA- Indoor electronic control P.C. board Timer short mode point JPG JPS (Refer to 7-1.) Room temperature thermistor RT11 (CN111) Indoor coil thermistor RT12, RT13 (CN112) Vane motor (CN151) Room temperature thermistor (RT11) Indoor coil thermistor (RT12, RT13) Connector to Indoor power P.C.
Page 37
MSZ-GE06/09/12/15/18NA- MSY-GE09/12/15/18NA- Indoor power P.C. board, Indoor terminal P.C. board Indoor terminal P.C. board Indoor power P.C. board Varistor (NR11) Resistor (R111) Fuse (F11)( ) Indoor fan motor (CN211) (+)0-6 V (+)3-6 VDC 15 VDC (–) GND (high- voltage DC) 294/325 VDC Terminal block...
Page 38
MSZ-GE24NA 3. Indoor terminal P.C. board, Indoor electronic control P.C. board, Power monitor receiver SW P.C. board Indoor terminal P.C. board Indoor electronic control P.C. board To disable "Auto restart function", Indoor coil thermistor Fuse solder the Jumper wire to JR07. Resistor Terminal Varistor...
Page 39
MSY-GE24NA Indoor terminal P.C. board, Indoor electronic control P.C. board, Power monitor receiver SW P.C. board Indoor terminal P.C. board Indoor electronic control P.C. board Indoor coil thermistor To disable "Auto restart function", Fuse Terminal Varistor Resistor RT12, RT13 12 VDC solder the Jumper wire to JR07.
Pull the terminal while pull out the terminal pushing the locking slowly. Locking lever lever. Connector 10-1. MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA NOTE: Turn OFF the power supply before disassembly. OPERATING PROCEDURE PHOTOS 1. Removing the panel Photo 1 (1) Remove the horizontal vanes.
Page 41
OPERATING PROCEDURE PHOTOS Electrical box 2. Removing the indoor electronic control P.C. Photo 2 Ground wire board and the room temperature thermistor (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the screw of the V.A. clamp and the V.A. Screw of the clamp.
Page 42
OPERATING PROCEDURE PHOTOS 4. Removing the nozzle assembly Photo 5 (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the indoor/outdoor connecting wire (Refer to 2 (2)-(7).). (3) Remove the indoor electronic control P.C. board hold- (4) Pull out the drain hose from the nozzle assembly and remove the nozzle assembly.
Page 43
OPERATING PROCEDURE PHOTOS 6. Removing the indoor fan motor, the indoor coil Photo 6 thermistor, and the line flow fan (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the indoor electronic control P.C. board hold- er, the electrical box and the nozzle assembly.
Page 44
10-2. MSZ-GE24NA MSY-GE24NA NOTE: Turn OFF the power supply before disassembly. OPERATING PROCEDURE PHOTOS 1. Removing the panel Photo 1 (1) Remove the horizontal vanes. Horizontal vanes Front panel (2) Remove the screw caps of the panel. Remove the screws of the panel. (3) Hold the lower part of both ends of the panel and pull it slightly toward you, and then remove the panel by pushing it upward.
Page 45
OPERATING PROCEDURE PHOTOS 4. Removing the nozzle assembly Photo 4 (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the V.A. clamp, and then the indoor/outdoor connecting wire. (Refer to 2 (2)-(4).) (3) Remove the electrical cover. (Photo 2) (4) Disconnect the following connectors on the electronic control P.C.
Page 46
OPERATING PROCEDURE PHOTOS 7. Removing the water cut, the indoor fan motor, Photo 8 the indoor coil thermistor, and the line flow fan (1) Remove the panel (Refer to 1.) and the corner box. (2) Remove the power monitor receiver holder, the electri- cal box and the nozzle assembly.
Page 47
Fixing the indoor coil thermistor There are 2 forms of parts for fixing the indoor coil thermistor. When fixing the indoor coil thermistor to the clip-shape/holder-shape part, the Clip shape Holder shape lead wire should point down. About the same length Position and procedure for mounting the clip-shape part 1.