Installing the Air Flow Regulator
This chapter explains how to install the regulators to maintain the air flow for ANSI and ETSI configurations
in NCS 2002 shelf.
The air flow within the equipment must be maintained at a nominal temperature. This task can be accomplished
using one of these mechanisms:
• Air deflector
• Air plenum
The sections are:
Air Deflector
An air deflector is a sheet-metal part that is mounted on the NCS 2002 shelf to orient the air flow in a specific
direction.
The air deflectors can be mounted in different positions to control the air flow:
• Front to Front— Only ETSI rack
• Front to Back— For ANSI and ETSI racks
• Front to Top— Only ETSI rack
In an ANSI rack, the air deflectors are mounted only on the 23-inch rack configuration.
Air Plenum
Air plenum orients the air flow in the front-to-back direction inside the equipment to be compliant with GR-63
issue 4 requirement.
NCS 2002 air plenum kit has one horizontal and two vertical air plenums. The air that flows from the front
top inlet are channelized to the right vertical plenum, inside the equipment, and then to the exhaust air channel
towards the left vertical air plenum. The air flow is deflected by 90 degrees and exited out in the rear end.
The following figure shows the air flow inside the air plenum.
Air Deflector, on page 1
Air Plenum, on page 1
Air Plenum Rack and Cabinet Compatibility, on page 3
NTP-L42 Install the Air Plenum in NCS 2002 Shelf, on page 4
Installing the Air Flow Regulator
1

Advertisement

Table of Contents
loading

Summary of Contents for Cisco NCS 2002

  • Page 1 NTP-L42 Install the Air Plenum in NCS 2002 Shelf, on page 4 Air Deflector An air deflector is a sheet-metal part that is mounted on the NCS 2002 shelf to orient the air flow in a specific direction. The air deflectors can be mounted in different positions to control the air flow: •...
  • Page 2 Figure 1: Air flow within the air plenum The following figures show the dimensions of the air plenum relative to the cabinet or rack. Figure 2: Dimension of Cisco NCS 2002 chassis relative to the air plenum Installing the Air Flow Regulator...
  • Page 3: Air Plenum Rack And Cabinet Compatibility

    Installing the Air Flow Regulator Air Plenum Rack and Cabinet Compatibility Figure 3: Dimension of Cisco NCS 2002 chassis relative to the air plenum Air Plenum Rack and Cabinet Compatibility The table shows the compatibility of air plenum with the ANSI and ETSI racks and cabinets. The chassis can be installed with brackets in front position only.
  • Page 4: Ntp-L42 Install The Air Plenum In Ncs 2002 Shelf

    Installing the Air Flow Regulator NTP-L42 Install the Air Plenum in NCS 2002 Shelf Figure 4: Minimum rear opening for ANSI 19-inch and ETSI configuration NTP-L42 Install the Air Plenum in NCS 2002 Shelf Purpose This procedure installs the air plenum to orient the air flow in front-to- back direction in the NCS 2002 shelf.
  • Page 5: Dlp-L65 Installing Air Plenum For Ncs 2002 Shelf In Ansi 19-Inch Configuration

    DLP-L71 Installing Pre-assembled Air Plenums in ANSI 23-inch Configuration, on page 12 Stop. You have completed this procedure. DLP-L65 Installing Air Plenum for NCS 2002 Shelf in ANSI 19-inch Configuration This task installs the air plenum for the NCS 2002 shelf in ANSI 19-inch cabinet or Purpose rack configuration.
  • Page 6 Installing the Air Flow Regulator DLP-L65 Installing Air Plenum for NCS 2002 Shelf in ANSI 19-inch Configuration Tools/Equipment • #2 Phillips Dynamometric screwdriver • Medium slot-head screwdriver • Small slot-head screwdriver • Screws: #12-24 x 0.50 pan-head Phillips screws (4) •...
  • Page 7 Installing the Air Flow Regulator DLP-L65 Installing Air Plenum for NCS 2002 Shelf in ANSI 19-inch Configuration Figure 6: Installing the left vertical air plenum Step 4 Install the vertical air plenum to the right of the horizontal air plenum. Follow step 3a to 3c.
  • Page 8: Dlp-L69 Installing Air Plenum In Ncs 2002 Shelf For Ansi 23-Inch Configuration

    Return to your originating procedure (NTP). DLP-L69 Installing Air Plenum in NCS 2002 Shelf for ANSI 23-inch Configuration Purpose This task installs the air plenum for the NCS 2002 shelf in the ANSI 23-inch cabinet or rack configuration. Tools/Equipment • #2 Phillips Dynamometric screwdriver •...
  • Page 9 Installing the Air Flow Regulator DLP-L69 Installing Air Plenum in NCS 2002 Shelf for ANSI 23-inch Configuration Procedure Step 1 Install the ANSI 23-inch adapter plates on the horizontal air plenum. Step 2 Align the screws to fix the adapter plates to the shelf. Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
  • Page 10 Installing the Air Flow Regulator DLP-L69 Installing Air Plenum in NCS 2002 Shelf for ANSI 23-inch Configuration Figure 10: Installing the horizontal air plenum in the ANSI 23-inch configuration Step 5 Install the vertical air plenum to the left of the horizontal air plenum: a) Insert the vertical air plenum in the free space between the horizontal air plenum and cabinet.
  • Page 11 Installing the Air Flow Regulator DLP-L69 Installing Air Plenum in NCS 2002 Shelf for ANSI 23-inch Configuration Figure 12: Installing the right vertical air plenum Step 7 Install ANSI 19-inch standard brackets on both sides of the chassis in front position. See...
  • Page 12: Dlp-L71 Installing Pre-Assembled Air Plenums In Ansi 23-Inch Configuration

    DLP-L71 Installing Pre-assembled Air Plenums in ANSI 23-inch Configuration DLP-L71 Installing Pre-assembled Air Plenums in ANSI 23-inch Configuration Purpose This task installs pre-assembled air plenums for the NCS 2002 shelf in the ANSI 23-inch configuration. Tools/Equipment • #2 Phillips Dynamometric screwdriver •...
  • Page 13: Dlp-L70 Installing Air Plenum For Ncs 2002 Shelf In Etsi Configuration

    Return to your originating procedure (NTP). DLP-L70 Installing Air Plenum for NCS 2002 Shelf in ETSI Configuration Purpose This task installs the air plenum for the NCS 2002 shelf in the ETSI configuration. Tools/Equipment • #2 Phillips Dynamometric screwdriver • Medium slot-head screwdriver •...
  • Page 14 Installing the Air Flow Regulator DLP-L70 Installing Air Plenum for NCS 2002 Shelf in ETSI Configuration Figure 16: Installing the adapter plates on the horizontal air plenum Step 3 Place the horizontal plenum above the chassis slot in the ETSI cabinet.
  • Page 15 Installing the Air Flow Regulator DLP-L70 Installing Air Plenum for NCS 2002 Shelf in ETSI Configuration b) Install the wing head screws from the internal side of the horizontal plenum as shown in the following figure. c) Tighten the screws to a torque value of 11.5 in-lb (1.3 N-m).
  • Page 16 Installing the Air Flow Regulator DLP-L70 Installing Air Plenum for NCS 2002 Shelf in ETSI Configuration Figure 20: Installing the NCS 2002 chassis below the horizontal air plenum Step 9 Return to your originating procedure (NTP). Installing the Air Flow Regulator...