hit counter script

Starting The Switch - Cisco Nexus 9332D-GX2B Hardware Installation Manual

Nx-os mode switch
Hide thumbs Also See for Nexus 9332D-GX2B:
Table of Contents

Advertisement

Installing the Chassis
1
2
Step 3
Secure the grounding lug to the chassis grounding pad with two M4 screws, see the previous figure. Tighten the screws
to 11 to 15 in-lb (1.24 to 1.69 N·m) of torque.
Step 4
Prepare the other end of the grounding wire and connect it to the facility ground.

Starting the Switch

You start the switch by connecting it to its dedicated power source. If you need n+1 redundancy, you must
connect each of the power supplies to one or two power sources. If you need n+n redundancy, you must
connect each power supply in a switch to a different power source.
Note
This equipment is designed to boot up in less than 30 minutes, dependent on its neighboring devices being
fully up and running.
Before you begin
• The switch must be installed and secured to a rack or cabinet.
• The switch must be adequately grounded.
• The rack must be close enough to the dedicated power source so that you can connect the switch to the
• You have the designated power cables for the power supplies that you are connecting to the dedicated
Chassis grounding pad
Grounding cable, with 0.75
in. (19 mm) of insulation that
is stripped from one end,
which is inserted into the
grounding lug and crimped
in place
power source by using a designated power cables.
power sources.
Cisco Nexus 9332D-GX2B NX-OS Mode Switch Hardware Installation Guide
3
Starting the Switch
2 M4 screws are used to
secure the grounding lug to
the chassis
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

N9k-c9332d-gx2b

Table of Contents