Revision D: • MSZ-GA•NA and MSY-GA•NA have been added. SPLIT-TYPE AIR CONDITIONERS Please void OB450 REVISED EDITION-C. INDOOR UNIT No. OB450 SERVICE MANUAL REVISED EDITION-D Models MSZ-A09NA, - MSZ-A12NA, - MSZ-A15NA, - MSZ-A17NA, - MSZ-A24NA, - MSY-A15NA, - MSY-A17NA, - MSY-A24NA, - Outdoor unit service manual MSZ-GA24NA...
Page 2
Revision A: • PARTS LIST has been revised. (10-1.8, 10-2.8) Revision B: • MSZ-A•NA- and MSY-A•NA- Remote controller has been changed. Revision C: • SPECIFICATION has been corrected. Powerful has been added. (Airflow , Sound level) Revision D: • MSZ-GA•NA and MSY-GA•NA have been added.
TECHNICAL CHANGES MSZ09UN MSZ-A09NA MSH24WN MSZ-A24NA MSZ12UN MSZ-A12NA MS15TN MSY-A15NA MSH15TN MSZ-A15NA MS17TN MSY-A17NA MSH17TN MSZ-A17NA MS24WN MSY-A24NA 1. Control method between indoor and outdoor has been changed. 2. Indoor fan motor has been changed. 3. Signal of remote controller has been changed. (It is not available for conventional models.) MSZ-A09NA MSZ-A09NA MSZ-A24NA...
PART NAMES AND FUNCTIONS MSZ-A09NA MSY-A15NA MSZ-A24NA MSY-A24NA MSZ-A12NA MSY-A17NA MSZ-GA24NA MSY-GA24NA MSZ-A15NA Front panel MSZ-A17NA Air inlet Heat exchanger Panel Air cleaning filter (Anti-Allergy Enzyme Filter, Blue bellows type) Catechin air filter Air outlet Vertical vane Remote controller Horizontal vane Line flow fan MSZ-A09NA Display section...
SPECIFICATION Indoor unit model MSZ-A09NA MSZ-A12NA External nish White Power supply V, phase, Hz 208/230, 1, 60 Max.-fuse size (time delay) / Disconnect switch Min. circuit ampacity Fan motor F.L.A 0.76 152-229-307-338 152-240-353-388 COOL Dry (Wet) Air ow (134-205-275-303) (134-215-318-349) Low–Med.–High–Powerful HEAT 159-222-307-321...
Page 6
3-1. OPERATING RANGE (1) POWER SUPPLY Rated voltage Guaranteed Voltage (V) 208/230 V Min.187 Max.253 Indoor unit 1 phase 60 Hz (2) OPERATION Intake air temperature (°F) Mode Condition Indoor Outdoor Standard temperature — Maximum temperature — Cooling Minimum temperature —...
SERVICE FUNCTIONS MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSZ-A24NA MSY-A15NA MSY-A17NA MSY-A24NA MSZ-GA24NA MSY-GA24NA 7-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS on the indoor electronic control P.C. board. The time will be shortened as follows. (Refer to 8-7.) Set time: 1-minute 1-second Set time: 3-minute...
7-3. AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure.
Page 12
3. Troubleshooting procedure 1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing ON and OFF before starting service work. 2) Before servicing check that the connector and terminal are connected properly.
Page 13
8-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (8-4.) disappears, the memorized failure details can be recalled. 1.
Page 14
2. Indoor unit failure mode table Left lamp of OPERATION Abnormal point Condition Correspondence INDICATOR lamp (Failure mode) Not lighted Normal — — The room temperature thermistor short or 1-time ash every Room temperature Refer to the characteristics of the room temperature open circuit is detected every 8 seconds dur- 0.5-second thermistor...
Page 15
8-3. INSTRUCTION OF TROUBLESHOOTING Start Indoor unit operates. Indoor unit oper- Indoor unit does OPERATION INDICATOR Outdoor unit does not receive the ates. lamp on the indoor unit is not operate normally. signal from re- Outdoor unit ashing ON and OFF. mote controller.
Page 16
8-4. TROUBLESHOOTING CHECK TABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes. OPERATION INDICATOR Lighted Blinking...
Page 17
OPERATION INDICATOR Abnormal Operation indicator lamp Symptom Condition Correspondence point Left lamp lights and lower lamp ashes. The operation mode of the each indoor unit MXZ type Outdoor unit is differently set to COOL (includes DRY) and • Unify the operation mode. Operation operates but HEAT at the same time, the operation mode...
Page 18
8-6. TROUBLESHOOTING FLOW A Check of indoor fan motor The indoor fan motor error has occurred, and the indoor fan does not operate. Turn OFF the power supply. Pay careful attention to the high voltage on the fan motor connector CN211. Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch.
Page 19
B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner. Press OPERATE/STOP (ON/OFF) button on the remote controller. Is LCD display on the remote controller Replace the batteries. (Refer to 8-1.4.) visible? (Not clear) Remove the batteries, then set them back...
Page 20
C Check of indoor electronic control P.C. board and indoor fan motor Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply. Measure the resistance between Short/open circuit: CN211...
Page 21
D How to check miswiring and serial signal error Turn OFF the power supply. Is there rated voltage in the Check the power supply. power supply? Turn ON the power supply. Is there rated voltage between outdoor terminal block S1 and Check the wiring.
Page 22
E Electromagnetic noise enters into TV sets or radios Is the unit grounded? Ground the unit. Is the distance between the antennas Extend the distance between the antennas and and the indoor unit within 9.91 ft., or is the indoor unit, and/or the antennas and the the distance between the antennas and outdoor unit.
Page 23
8-7. Test point diagram and voltage MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSY-A15NA MSY-A17NA Indoor electronic control P.C. board Power supply input Varistor (NR11) 208/230 VAC Fuse (F11) 250 V 3.15 A Resistor (R111) Indoor fan motor (CN211) 294/325 VDC (-) Fiducial terminal of cathode side on measur- ing high-voltage DC 15 VDC...
Page 24
MSZ-A24NA MSY-A24NA MSZ-GA24NA MSY-GA24NA Indoor electronic control P.C. board Resistor Release of Auto restart Power supply input (R111) function Varistor (NR11) 208/230 VAC Fuse (F11) Solder the Jumper wire 250 V 3.15 A to JR07 (Refer to 7-3.) Indoor fan motor (CN211) 294/325 VDC (-) Fiducial terminal of...
DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
Page 26
OPERATING PROCEDURE PHOTOS 2. Removing the electronic control P.C. board, the Photo 4 power monitor receiver P.C. board, SW P.C. board and the terminal block (1) Remove the horizontal vane, the panel (refer to 1.) and the corner box. (2) Remove the screw of the conduit cover, and conduit cover. (Photo 2 or Photo 3) (3) Remove the indoor/outdoor connecting wire.
Page 27
OPERATING PROCEDURE PHOTOS 4. Removing the horizontal vane motor unit Photo 7 (1) Remove the horizontal vane, the panel (refer to 1.) and the corner box. (2) Remove the screws of the horizontal vane motor unit, and Screws of the pull out the horizontal vane motor unit.
Page 28
9-2. MSZ-A24NA MSY-A24NA MSZ-GA24NA MSY-GA24NA OPERATING PROCEDURE PHOTOS 1. Removing the front panel Photo 1 Front panel (1) Remove the screw caps of the front panel. Remove the screws. (2) Pull the panel down to your side slightly and unhook the catches at the top.
Page 29
OPERATING PROCEDURE PHOTOS 4. Removing the vane motor Photo 4 (1) Remove the front panel. (Refer to 1.) (2) Remove the electrical cover. (Refer to 2.) Vane motors Screws (3) Remove the lead wire of vane motor. (Refer to 3.) of the (4) Remove the R.L.
PARTS LIST 10-1. PARTS LIST (non-RoHS compliant) MSZ-A09NA MSZ-A12NA MSY-A15NA MSY-A17NA MSZ-A15NA MSZ-A17NA 1. INDOOR UNIT STRUCTURAL PARTS 2. ACCESSORY AND REMOTE CONTROLLER (See 10-1.5.) 1. INDOOR UNIT STRUCTURAL PARTS Q'ty/unit Symbol Part No. Part name in Wiring MSZ- MSY- Remarks Diagram A09NA A12NA A15NA A17NA A15NA A17NA...
Page 31
MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSY-A15NA MSY-A17NA 3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS Q'ty/unit Symbol Part No. Part name in Wiring MSZ- MSY- Remarks Diagram A09NA A12NA A15NA A17NA A15NA A17NA 1 E02 751 509 BEARING MOUNT 2 E02 001 504 SLEEVE BEARING 3 E02 897 702 DRAIN HOSE...
Page 32
MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSY-A15NA MSY-A17NA 4. INDOOR UNIT HEAT EXCHANGER Q'ty/unit Symbol MSZ- MSY- Part No. Part name in Wiring Remarks Diagram A09NA A12NA A15NA A17NA A15NA A17NA E02 A54 620 INDOOR HEAT EXCHANGER E02 A56 620 E02 815 666 ø3/8 UNION (GAS) E02 155 666...
Page 33
MSZ-A24NA MSY-A24NA 6. INDOOR UNIT STRUCTURAL PARTS 7. INDOOR UNIT HEAT EXCHANGER (See 10-1.10.) 6. INDOOR UNIT STRUCTURAL PARTS Part number that is circled is not shown in the illustration. Symbol Q'ty/unit Part No. Part Name in Wiring Remarks MSZ-A24NA MSY-A24NA Diagram 1 E02 527 970...
Page 34
MSZ-A24NA MSY-A24NA 9. ACCESSORY AND 8. INDOOR UNIT FUNCTIONAL PARTS AND REMOTE CONTROLLER ELECTRICAL PARTS 8. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS Part numbers that is circled is not shown in the illustration. Symbol Q'ty/unit Part No. Part Name in Wiring Remarks MSZ-A24NA...
Page 35
10. AIR CLEANING FILTER (ANTI-ALLERGY ENZYME FILTER) AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity. Normal life of AIR CLEANING FILTER is 1 year. If AIR CLEANING FILTER is to be washed, soak AIR CLEANING FILTER in water (when showing dirt, in lukewarm water) and rinse it delicately, without removing the filter from the frame about once every 3 months.
10-2. RoHS PARTS LIST (RoHS compliant) MSZ-A09NA MSZ-A12NA MSY-A15NA MSY-A17NA MSZ-A15NA MSZ-A17NA 2. ACCESSORY AND REMOTE 1. INDOOR UNIT STRUCTURAL PARTS CONTROLLER (See 10-2.5.) 1. INDOOR UNIT STRUCTURAL PARTS Q'ty/unit Symbol MSZ-A MSY-A Part No. Part name in Wiring Remarks 09NA 12NA 15NA...
Page 37
MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSY-A15NA MSY-A17NA 3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS Q'ty/unit Symbol MSZ-A MSY-A Part No. Part name in Wiring Remarks 09NA 12NA 15NA 17NA 15NA 17NA Diagram 1 G E12 751 509 BEARING MOUNT 2 G E12 001 504 SLEEVE BEARING 3 G E12 897 702 DRAIN HOSE...
Page 38
MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSY-A15NA MSY-A17NA 4. INDOOR UNIT HEAT EXCHANGER Q'ty/unit Symbol MSZ-A MSY-A Part No. Part name in Wiring Remarks 09NA 12NA 15NA 17NA 15NA 17NA Diagram G E12 A54 620 INDOOR HEAT EXCHANGER G E12 A56 620 G E12 815 666 ø3/8 UNION (GAS)
Page 39
MSZ-A24NA MSY-A24NA MSZ-GA24NA MSY-GA24NA 6. INDOOR UNIT STRUCTURAL PARTS 7. INDOOR UNIT HEAT EXCHANGER (See 10-2.10.) 6. INDOOR UNIT STRUCTURAL PARTS Part number that is circled is not shown in the illustration. Q'ty/unit Symbol MSZ- MSY- Part No. Part Name in Wiring Remarks A24NA...
Page 40
MSZ-A24NA MSY-A24NA MSZ-GA24NA MSY-GA24NA 8. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol MSZ- MSY- Part No. Part Name in Wiring Remarks A24NA A24NA GA24 GA24 Diagram G E12 527 302 LINE FLOW FAN G E12 408 509 BEARING MOUNT...
Page 41
MSZ-A24NA MSY-A24NA MSZ-GA24NA MSY-GA24NA 9. ACCESSORY AND REMOTE CONTROLLER Q'ty/unit Symbol MSZ- MSY- Part No. Part Name in Wiring Remarks A24NA A24NA GA24 GA24 Diagram G E12 A58 426 KM06B G E12 A53 426 KM06D REMOTE CONTROLLER G E12 C26 426 KM07K G E12 C29 426 KM07M...
MICROPROCESSOR CONTROL MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSZ-A24NA MSY-A15NA MSY-A17NA MSY-A24NA MSZ-GA24NA MSY-GA24NA WIRELESS REMOTE CONTROLLER These pictures show MSZ-A24. Signal transmitting section (This diagram shows an overall view.) Operation display section ON/OFF (operate/ stop) button VANE button (Horizontal vane button) Fan speed control button Temperature buttons...
Page 43
11-1. COOL ( ) OPERATION (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 61 ~ 88°F.
Page 44
(4) The initial set temperature is decided by the initial room temperature. Initial room temperature Model Initial set temperature 79°F or more 75°F COOL mode of "I FEEL CONTROL" 77 to 79°F Initial room temperature minus 4°F Less than 77°F DRY mode of "I FEEL CONTROL"...
Page 45
11-7. AUTO VANE OPERATION 1. Horizontal vane (1) Vane motor drive These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12 V) transmitted from indoor microprocessor. (2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
Page 46
(9) To change the air ow direction not to blow directly onto your body. (MSZ-A09/12/15/17, MSY-A15/17) HEAT To change the air ow When to use this function? COOL/DRY direction (For MSZ) Pressing and holding Use this function if you do The air conditioner starts the The air conditioner starts heating VANE CONTROL button...
Page 47
(5) WIDE MODE ( By selecting WIDE mode with WIDE VANE button, indoor fan speed becomes faster than setting fan speed on the remote controller ( ). The remote controller displays “ ”. NOTE: The position of vane angle 3, angle 4 and angle 5 are different in COOL operation and HEAT operation. Indoor fan speed becomes faster than setting fan speed on the remote controller even when selected.