hit counter script
Sanyo COOL Installation Instructions Manual
Sanyo COOL Installation Instructions Manual

Sanyo COOL Installation Instructions Manual

Split system air conditioner
Table of Contents

Advertisement

In order to protect the environment, this air conditioner uses the new refrigerant R410A.
Contents
Please Read Before Starting .................................. 1
1.
GENERAL .......................................................... 2
2.
INSTALLATION SITE SELECTION ................... 3
3.
4.
POSITION ........................................................ 14
5.
ADDRESS SWITCHES ..................................... 15
6.
85464359328000 © SANYO 2002
INSTALLATION INSTRUCTIONS
- Split System Air Conditioner -
Page
SANYO FISHER COMPANY
A DIVISION OF SANYO NORTH AMERICA CORPORATION
21605 Plummer Street
Chatsworth, CA 91311 U.S.A.
Model Combinations
Combine indoor and outdoor units only as listed
below.
KS2462R
Power supply: 60Hz, single-phase, 208/230V
Units should be installed by a licensed contractor
according to local code requirements.
7.
ELECTRICAL WIRING ..................................... 17
8.
HOW TO PROCESS TUBING .......................... 19
9.
AIR PURGING................................................... 22
10. TEST RUN......................................................... 25
WHEN INSTALLING UNIT................................ 28
COOL/DRY Model
C2462R
CL2462R
In Canada
SANYO Canada Inc.
300 Applewood Crescent
Concord, Ontario
L4K 5C7, Canada

Advertisement

Table of Contents
loading

Summary of Contents for Sanyo COOL

  • Page 1: Table Of Contents

    11-3. Tools Specifically for R410A 11-4. Charging Additional Refrigerant In Canada SANYO FISHER COMPANY SANYO Canada Inc. A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent 21605 Plummer Street Concord, Ontario 85464359328000 © SANYO 2002 Chatsworth, CA 91311 U.S.A.
  • Page 2: Important

    IMPORTANT! When Installing… Please Read Before Starting …In a Ceiling, Wall or Floor This air conditioning system meets strict safety and operat- Make sure the ceiling/wall/floor is strong enough to hold ing standards. As the installer or service person, it is an the unit’s weight.
  • Page 3: General

    1. General 6. Sabre saw or key hole saw This booklet briefly outlines where and how to install the 7. Hacksaw air conditioning system. Please read over the entire set 8. Core bits of instructions for the indoor and outdoor units and make 9.
  • Page 4: Additional Materials Required For Installation

    1-6. Additional Materials Required for Installation Indoor unit Refrigeration (armored) tape Insulated staples or clamps for connecting wire (See local codes) Putty Refrigeration lubricant Clamps or saddles to secure refrigerant tubing Drain hose 1-7. Operating Range Outside drainage Fig. 1 Temperature Indoor Air Intake Outdoor Air Intake...
  • Page 5: Outdoor Unit

    Heat source heat sources, exhaust fans, etc. (Fig. 4a) damp, humid or uneven locations. Outdoor unit choose a place as cool as possible. choose a place that is well ventilated. Fig. 4a allow enough room around the unit for air intake/ exhaust and possible maintenance.
  • Page 6: Wind Shield For "Cl" Model

    2-4. Wind Shield for “CL” Model Wind shield (air discharge side) IMPORTANT It is recommended to use wind shields for “CL” model (Fig. 5b). “CL” model is designed to use in low outdoor temperature conditions. Front General When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air tempera- ture in winter), a suitable wind shield must be installed on the outdoor unit.
  • Page 7: How To Install The Indoor Unit

    3. How to Install the Indoor Unit 3-1. Remove the Rear Panel from the Unit Remove and discard the set screws and take off the rear panel. (Fig. 6) NOTE Tubing can be extended in 3 directions as shown in Set screws for transportation only Fig.
  • Page 8: Install The Rear Panel On The Wall

    3-3. Install the Rear Panel on the Wall Be sure to confirm that the wall is strong enough to sus- pend the unit. See either Item a) or b) below depending on the wall type. a) If Wooden Wall Fig. 11 (1) Attach the rear panel to the wall with the 10 screws provided.
  • Page 9: Shape The Indoor Side Tubing

    How to replace the grille (1) Close the flaps. (2) Reinstall the grille into the lower part while aligning its tabs on the upper part. (Fig. 15a) Insert the tabs in the slots and push the lower part of the grille back into position.
  • Page 10: Recommended Wire Length And Diameter

    3-7. Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regu- lations when carrying out the installation. Table 5 lists recommended wire lengths and diameters for power supply systems.
  • Page 11: Wiring Instructions For Inter-Unit Connections

    3-8. Wiring Instructions for Inter-unit Connections (1) Insert the inter-unit wiring (according to local codes) into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 10 inches to Rear Wall extend from the wall face. (Fig. 19) panel Plastic (2) Route the inter-unit wiring from the back of the...
  • Page 12 Solid wire Loose wiring may cause the WARNING Loop terminal to overheat or result in unit malfunction. A fire haz- ard may also exist. Therefore, be sure all wiring is tightly Insulation connected. Fig. 21a When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal”...
  • Page 13: Mounting

    3-9. Mounting Right-side tubing (1) Shape the refrigerant tubing so that it can easily go Cover into the wall hole. (Fig. 24) Refrigerant tubing If using a stepladder, be careful CAUTION to keep your balance and not fall off. To prevent the unit Inter-unit wiring from damage and avoid per-...
  • Page 14: Drain Hose

    3-10. Drain Hose a) The drain hose should be slanted downward to the Slant outdoors. (Fig. 28) b) Never form a trap in the course of the hose. Indoor Drain If the drain hose will run in the room, insulate the unit hose hose with insulation * so that chilled condensation...
  • Page 15: Remote Control Unit Installation Position

    4. Remote Control Unit Installation Position The remote control unit can be operated from either a non-fixed position or a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places: In direct sunlight Behind a curtain or other place where it is covered More than 26 ft.
  • Page 16: Address Switches

    5. Address Switches Change the address switch to prevent mixing of sig- nals from remote control units when 2 Sanyo air con- ditioners are installed next to each other. Normally, the address switch is set to A. To change the address...
  • Page 17: How To Install The Outdoor Unit

    6. How to Install the Outdoor Unit Compressor 6-1. Removing the Packing Skid Remove the packing skid from the bottom. (Fig. 34) Place the unit on a level concrete pad, block or equal and anchor. Refer to Section 2. “Installation Site Selection.” Packing skid 6-2.
  • Page 18: Indoor Unit Outdoor Units

    7. Electrical Wiring (7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your 7-1. General Precautions on Wiring LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all (1) Before wiring, confirm the rated voltage of the unit relevant rules and regulations.
  • Page 19: Examples Of Incorrect Wiring

    CAUTION 7-4. Examples of Incorrect Wiring The following are examples of improper wiring that result in system misoperation. You should confirm that you have wired the units correctly before beginning the Test Run described on page 25. Problem 1 Short circuit will occur after approx. 3 minutes. Indoor unit Outdoor unit Problem 2...
  • Page 20: How To Process Tubing

    8. How to Process Tubing (See 11. REFRIGERANT R410A: SPECIAL PRECAUTIONS) Deburring The narrow tubing side is connected by a flare nut, and the wide tubing side is connected by brazing. Before After 8-1. Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.
  • Page 21: Precautions During Brazing

    Do not allow the tubing to get too hot during the brazing process. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to 2. Mount the rear panel become damaged. Therefore allow the tubing to cool 1. Cut hole between brazings. in wall 8-5.
  • Page 22: Connecting Tubing Between Indoor And Outdoor Units

    8-6. Connecting Tubing between Indoor and Outdoor Units Torque wrench a) Tightly connect the indoor side refrigerant tubing extended from the wall with the outdoor side tubing. (Fig. 41) Spanner Indoor unit b) To fasten the flare nuts, apply specified torque as: Table 6 Outdoor unit Tube Dia.
  • Page 23: Air Purging

    Manifold valve 9. Air Purging Air and moisture remaining in the refrigerant system Pressure have undesirable effects as indicated below. Therefore, gauge they must be purged completely. pressure in the system rises Charge hose operating current rises cooling (or heating) efficiency drops moisture in the air may freeze and block capillary tub- Nitrogen gas cylinder (In vertical standing...
  • Page 24 Manifold valve To prevent nitrogen from enter CAUTION the refrigerant system in the Pressure liquid state, the top of the gauge cylinder must be higher than the bottom when you pres- surize the system. Usually, the cylinder is used in a vertical standing position.
  • Page 25 Charging additional refrigerant Wide tube Use a charging cylinder CAUTION Outdoor Indoor designed for use with R410A. unit unit Narrow tube Max. allowable Required tubing length additional Calculate the required amount of additional refrigerant at shipment charge according to narrow tube length (see P. 3, Table 3). 132 ft.
  • Page 26: Test Run

    10. Test Run 10-1. Preparing for Test Run Before starting the air conditioner, check the follow- ing: (1) Remove all loose matter from the cabinet especially metal filings, bits of wire, and clips. (2) Connect the control wiring correctly and tighten all elec- trical connections.
  • Page 27 Basic Functions of the Service Valves Narrow Tube Service Wide Tube Service Action Valve (3-Way) Valve (Ball Valve) CLOSED CLOSED O-ring Stem Shipping and air purging Fully Fully OPEN OPEN Operating and test running the air conditioner Narrow tube service valve Wide tube service valve Valve cap O-ring...
  • Page 28 Pump Down “Pump down” means collecting all refrigerant gas in the system back into the outdoor unit without losing any of the gas. Pump down is used when the unit is to be moved or before servicing the refrigerant circuit. Pump down procedure Be sure to carry out pump down CAUTION...
  • Page 29: Refrigerant R410A: Special Precautions When Installing Unit

    11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN INSTALLING UNIT 11-1. Characteristics of New Refrigerant R410A 11-1-1. What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture which do not adversely affect the earth’s ozone layer. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22.
  • Page 30 Tubing precautions Refrigerant R410A is more easily affected by dust or moisture compared to R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation. Never use 0.7mm-thick copper tubing or tubing which is less than 0.8mm in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C.
  • Page 31: Tools Specifically For R410A

    11-3. Tools Specifically for R410A For servicing, use the following tools for R410A Tool Distinction Tool Name Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with anti-reverse flow (*1) Tools specifically for R410A (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2) …...
  • Page 32: Charging Additional Refrigerant

    11-4. Charging Additional Refrigerant 11-4-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. Never charge additional refrigerant if refrigerant is leaking from the unit. CAUTION 11-5.

This manual is also suitable for:

DryKs2462rC2462rCl2462r

Table of Contents