[6-5 Making Interlock Settings from an MA Remote Controller ]
< 2. Search Procedures >
To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is
8
connected to it.
<Indoor unit address>
Press the [
MENU] button to search for the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
9
- Search completed (With a LOSSNAY connection)
The indoor unit address and
- Search completed (No interlocked settings with a LOSSNAY exist.)
- The selected address does not have a corresponding indoor unit.
< 3. Deletion Procedures >
Take the following steps to delete the interlock setting between a LOSSNAY unit and the interlocked indoor unit from the remote controller
that is connected to the indoor unit.
Find the address of the LOSSNAY to be deleted (See section 2. Search Procedures. ), and bring up the result of the search for both the
10
indoor unit and LOSSNAY on the display.
Press the [
ON/OFF] button twice to delete the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
11
- Registration completed
The indoor unit address and
-Deletion error
If the deletion fails
HWE13080
IC, and the interlocked LOSSNAY address and LC will appear alternately.
,
and the interlocked LOSSNAY address and
will appear alternately.