free stats

Initial Led Display - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents

Advertisement

[9-1 LED Status Indicators ]
9-1-2

Initial LED Display

From power on until the completion of initial settings, the following information will be displayed on the monitor screen.
(Displays No. 1 through No. 4 in order repeatedly.)
No
Item
Software version
1
Refrigerant type
2
Model and capacity
3
Communication address
4
After the initial settings have been completed, the information on these items can be checked by making the switch setting
that corresponds to No. 517 in the LED display table.
Only item No. 1 "Software Version" appears on the display if there is a wiring failure between the control board and the trans-
mission line power supply board or if the circuit board has failed.
HWE13080
Display
[0103] : Version 1.03
[ 410] : R410A
[H-20] : Cooling/Heating 20 HP
For the first few minutes after power on, the capacity of
each outdoor unit is displayed. Thereafter, the com-
bined capacity is displayed.
[ 51] : Address 51
- 326 -
Remarks
GB

Advertisement

Table of Contents
loading

Table of Contents

Save PDF