hit counter script
Download Print this page

Maximum Refrigerant Charge - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[6-3 Evaluating and Adjusting Refrigerant Charge ]
6-3-3

Maximum refrigerant charge

There is a limit to the amount of refrigerant that can be charged into a unit. Observe the maximum refrigerant charge in the
table below.
HP200, 250YNW-A
Total index of the outdoor units
Factory charge (kg)
Maximum additional refrigerant
charge on site (kg)
Maximum refrigerant charge (kg)
HP400, 500YSNW-A
Total index of the outdoor units
Factory charge (kg)
Maximum additional refrigerant
charge on site (kg)
Maximum refrigerant charge (kg)
BS_06_L
HP200
HP250
9.8
10.8
21.9
22.5
31.7
33.3
HP400
HP500
19.6
21.6
31.3
32.0
50.9
53.6