Download Print this page

Mitsubishi Electric PUHY-HP200YNW-A Service Handbook page 253

Advertisement

[8-12 Parts Replacement Instructions ]
(9) Remove the fan guard by unscrewing the 12 screws. (See Figure 7.)
(10) Insert a spacer between the control box and the heat exchanger.
(11) Remove the motor ASSY by unscrewing the 8 screws, using caution not to damage the motor wiring or the fan.
(See Figure 8.)
Figure 7
(12) Remove the front pillar by unscrewing the 7 screws. (See Figure 9.)
(13) Disconnect the TH7 sensor holder from the front pillar. (See Figure 9 Rear.)
(14) Remove the TH7 wiring from the heat exchanger by cutting the cable tie. (See Figure 10.)
Front pillar
Figure 9
*Use the supplied spacers.
Use the spacers 60 (D) x 250 (W) x 60 (H) when replacing the heat exchangers for the maintenance of the accumulator and the
pipes.
66
- chapter 8
Fan guard
Front heat exchanger
Spacer *
Control box
Front heat
exchanger
Connector
Front pillar
TH7
Rear
Spacer *
Motor ASSY
Figure 8
TH7
Remove the TH7 wiring from
the front heat exchanger.
Spacer *
Figure 10
Fan
Cable tie
BS_08_M

Advertisement

loading

This manual is also suitable for:

Puhy-hp250ynw-aPuhy-hp400ysnw-aPuhy-hp500ysnw-a