hit counter script
Download Print this page

Error Code [0404] - Mitsubishi Electric PUHY-HP200YNW-A Service Handbook

Advertisement

[7-2 Error Code Definitions and Solutions: Codes [0 - 999] ]
7-2-2

Error Code [0404]

1. Error code definition
Indoor unit control-related errors
2. Error definition and error detection method
Indoor controller board
Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board.
3. Cause, check method and remedy
Defective indoor controller board
Note: Refer also to the Service Handbook for the indoor units.
BS_07_L
Cause
Check method and remedy
Replace indoor controller board.
7
chapter 7 -

Advertisement

loading

This manual is also suitable for:

Puhy-hp250ynw-aPuhy-hp400ysnw-aPuhy-hp500ysnw-a