Power Supply Power Cord Specifications

Figure 31: HVAC Power Connection
Step 3
For HVDC input, connect a Saf-D-Grid DC cable to a Saf-D-Grid receptacle, otherwise:
a) Connect the ground terminal ring on the power cable to the ground terminal on the DC power source and
secure it in place with a nut tightened to the appropriate torque setting for the terminal post.
b) Connect the negative terminal ring on the power cable to the negative (-) terminal on the DC power source
and secure it in place with a nut tightened to the appropriate torque setting for the terminal post.
c) Connect the positive terminal ring on the power cable to the negative (+) terminal on the DC power source
and secure it in place with a nut tightened to the appropriate torque setting for the terminal post.
Step 4
Verify that the Saf-D-Grid plug is plugged in completely to secure the built-in retaining latch.
Step 5
Turn on the circuit breaker for the HVAC or HVDC power source circuit.
Note
Step 6
Turn on the switch of the power shelf to turn on the system.
What to do next
Use the power redundancy-mode mode command to specify one of the following power modes:
• For combined mode, include the combined keyword.
• For n+1 redundancy mode, include the ps-redundant keyword.
• For n+n redundancy mode, include the insrc-redundant keyword.
Example:
switch(config)# power redundancy-mode insrc-redundant
switch(config)#
Power Supply Power Cord Specifications
Note
Cisco Nexus 9808 NX-OS Mode Switch Hardware Installation Guide
46
If you use both inputs, the IN LED of the power supply is green. If you use only one input, the
IN LED is blinking green.
Always use the Saf-D-Grid connector toward the switch.
Powering on the Switch