Error Messages
F2026 Undervoltage in power section
Drive Controllers HMS, HMD,
Supply Unit HMV01.1
Cause
Power is switched off without previous drive
deactivation by means of drive enable ("AF")
Failure in power supply or overload of power supply
Mains failure
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
Supported by Supply Unit:
The DC bus voltage value is monitored by the drive controller and the
supply unit.
If the DC bus voltage falls below the minimum value determined for the
HCS
drive (see value of P-0-0114, Undervoltage threshold) or it reacts to
"DC bus not ok" of the module bus, the device generates the error
message F2026 if "non-fatal warning" has been set with regard to the
reaction to undervoltage in P-0-0118, Power supply, configuration.
If the DC bus voltage falls below 75% of the mains voltage crest value
that was detected when the mains contactor had been switched on, the
error F2026 is displayed at the device. Power is switched off!
See also Functional Description "Power Supply"
F2026 - Attributes
Display:
F2026
Mess. no.:
F2026 (hex)
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
HMV01
Remedy
Check logic for activating drive in connected control unit
Check power supply
Check cause of mains failure, switch mains voltage on
again