7-122
Error Messages
F2818 Phase failure
Cause
Mains circuit breaker defective
Incorrect wiring
F2819 Mains failure
Cause
Mains failure (permanent or temporary)
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Supply Unit:
A single-phase mains failure of more than 2 seconds was detected. The
device was switched off.
Remedy
Replace mains circuit breaker
Check and correct wiring
F2818 - Attributes
Display:
F2818
Mess. no.:
F2818 (hex)
Supported by Firmware Variant:
Supported by Supply Unit:
The mains has failed. The DC bus voltage has fallen below a threshold
value so that a new soft start process is required.
Remedy
Search and remove cause of mains failure
See also Functional Description "Power Supply"
F2819 - Attributes
Display:
F2819
Mess. no.:
F2819 (hex)
Rexroth IndraDrive
HMV01
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
HMV01
DOK-INDRV*-GEN-**VRS**-WA01-EN-P