C3206 Incorrect input for power
C3207 Type plate list incomplete
Cause
List length of parameter P-0-4032, Type plate list
asynchronous motor is shorter than 6 elements or
at least one element has value "0"
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
During the execution of the command P-0-4033, C3200 Command
Calculate data for asynchronous motor an error was detected.
Cause:
There is no useful relation between list element 6 (rated power) in
P-0-4032, Type plate list asynchronous motor and electric power that
results from the other rated data.
Effective electric power of an asynchronous motor results from
rated
current
Fig. 9-2:
Effective electric power of an asynchronous motor
Mechanical power output has to be smaller than above value because an
efficiency of less than 1 is assumed. Furthermore a mechanical power
output smaller than 40% of effective electric power is not plausible.
Remedy:
Correct values in P-0-4032, Type plate list asynchronous motor and
restart command P-0-4033, C3200 Command Calculate data for
asynchronous motor.
C3206 - Attributes
Display:
C3206
Mess. no.:
C3206 (hex)
Supported by Firmware Variant:
During the execution of the command P-0-4033, C3200 Command
Calculate data for asynchronous motor an error was detected.
Remedy
Please check: To calculate motor and controller
parameters from type plate of an asynchronous motor,
value higher than "0" has to be entered in all 6 list
elements of P-0-4032, Type plate list asynchronous
motor
C3207 - Attributes
Display:
C3207
Mess. no.:
C3207 (hex)
Command Diagnostic Messages
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
ϕ
×
×
rated
voltage
cos
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
9-115
×